Cable Cross-Section Calculator
Size a copper or aluminium cable for an allowed voltage drop in single-phase, DC or three-phase circuits, from current or power, and see the next standard size and its actual drop.
Enter positive values: length up to 10 000 m, cos φ 0.1–1, voltage drop up to 50 %.
This sizes the cable for voltage drop only. The final size must also carry the current without overheating (installation method, grouping, ambient temperature) and match the protective device under your local wiring rules; ask a qualified electrician.
How minimum cable cross-section is calculated
S = k·L·I·ρ·cos φ / ΔU; k = 2 (1~, DC), √3 (3~); ρ(Cu) = 0.0175, ρ(Al) = 0.0282 Ω·mm²/m; I = P / (U·cos φ) (1~), P / (√3·U·cos φ) (3~).
This sizes the cable for voltage drop only. The final size must also carry the current without overheating (installation method, grouping, ambient temperature) and match the protective device under your local wiring rules; ask a qualified electrician.
Frequently asked questions
Why use mm² instead of AWG for cable size?
Square millimeters (mm²) is the standard cable sizing unit in most of the world outside North America, which commonly uses AWG (American Wire Gauge) instead. Both describe the same physical property — the wire's cross-sectional area — just in different units.
What voltage drop limit should I use?
Many wiring rules aim for about 3 % on final circuits and 5 % in total from the supply; choose “Percent of the voltage” to enter the limit directly, and follow your local rules.
Should I round up to the next standard cable size?
Yes — cables are manufactured in standard sizes (like 1.5, 2.5, 4, 6, 10 mm², and so on), not arbitrary cross-sections. Always round your calculated minimum up to the next available standard size, never down.