Voltage Drop Calculator
Estimate resistive voltage drop for copper, aluminum or a measured conductor in single- or three-phase circuits.
Enter valid values within the supported ranges. Results are cleared for invalid or incomplete input.
Copper and aluminum estimates use K=12.9 and 21.2 Ω·cmil/ft at 75°C. Custom resistance is in Ω/km. Enter one-way length; the multiplier is 2 for DC/single-phase or √3 for balanced three-phase, using line-to-line source voltage. Assumes unity power factor and neglects reactance. A drop above source voltage is outside this model. This does not determine ampacity or certify compliance with electrical rules.
How voltage drop is calculated
Estimate resistive voltage drop for copper, aluminum or a measured conductor in single- or three-phase circuits.
Copper and aluminum estimates use K=12.9 and 21.2 Ω·cmil/ft at 75°C. Custom resistance is in Ω/km. Enter one-way length; the multiplier is 2 for DC/single-phase or √3 for balanced three-phase, using line-to-line source voltage. Assumes unity power factor and neglects reactance. A drop above source voltage is outside this model. This does not determine ampacity or certify compliance with electrical rules.
ΔV = k × I × L × R; k = 2 / √3; 1 ft = 0.3048 m.
Frequently asked questions
Why is the distance doubled in the calculation?
Copper and aluminum estimates use K=12.9 and 21.2 Ω·cmil/ft at 75°C. Custom resistance is in Ω/km. Enter one-way length; the multiplier is 2 for DC/single-phase or √3 for balanced three-phase, using line-to-line source voltage. Assumes unity power factor and neglects reactance. A drop above source voltage is outside this model. This does not determine ampacity or certify compliance with electrical rules.
What percentage voltage drop is acceptable?
Copper and aluminum estimates use K=12.9 and 21.2 Ω·cmil/ft at 75°C. Custom resistance is in Ω/km. Enter one-way length; the multiplier is 2 for DC/single-phase or √3 for balanced three-phase, using line-to-line source voltage. Assumes unity power factor and neglects reactance. A drop above source voltage is outside this model. This does not determine ampacity or certify compliance with electrical rules.
How do I reduce voltage drop on a long wire run?
Using a thicker wire (a lower AWG number) reduces resistance per foot and therefore voltage drop for the same current and distance. Shortening the distance or reducing the current drawn also reduces voltage drop.
Which resistance is used for mm² sizes and limits?
Metric sizes use the same 75 °C conductor constants as the AWG table (copper 12.9 and aluminium 21.2 Ω·cmil/ft, about 0.0215 and 0.0353 Ω·mm²/m), so results are a little higher than with 20 °C resistivity. The limit you enter is only compared with the calculated drop; the allowed drop and the cable size required for current capacity come from your local wiring rules.
How we verified this calculator
The calculator is checked against 6 reference cases computed independently of its code. Last passed: .
| # | Inputs | Expected result |
|---|---|---|
| 1 |
Conductor material = Copper at 75°C
Circuit type = DC or single-phase
Wire gauge (AWG) = 12 AWG
Length unit = Feet (ft)
Resistance (Ω/km) = 6.34
Current (A) = 10
One-way distance = 50
Source voltage (V) = 120
|
Voltage drop (V): 1.97549770291
Voltage drop (%): 1.64624808576
Receiving voltage (V): 118.024502297
Resistance (Ω/km): 6.48129167621
|
| 2 |
Conductor material = Aluminum at 75°C
Circuit type = DC or single-phase
Wire gauge (AWG) = 12 AWG
Length unit = Feet (ft)
Resistance (Ω/km) = 6.34
Current (A) = 10
One-way distance = 50
Source voltage (V) = 120
|
Voltage drop (V): 3.24655436447
Voltage drop (%): 2.70546197039
Receiving voltage (V): 116.753445636
Resistance (Ω/km): 10.6514250803
|
| 3 |
Conductor material = Copper at 75°C
Circuit type = Balanced three-phase
Wire gauge (AWG) = 12 AWG
Length unit = Feet (ft)
Resistance (Ω/km) = 6.34
Current (A) = 10
One-way distance = 50
Source voltage (V) = 120
|
Voltage drop (V): 1.71083119584
Voltage drop (%): 1.4256926632
Receiving voltage (V): 118.289168804
Resistance (Ω/km): 6.48129167621
|
| 4 |
Conductor material = Aluminum at 75°C
Circuit type = Balanced three-phase
Wire gauge (AWG) = 14 AWG
Length unit = Metres (m)
Resistance (Ω/km) = 6.34
Current (A) = 20
One-way distance = 10
Source voltage (V) = 400
|
Voltage drop (V): 5.86232240685
Voltage drop (%): 1.46558060171
Receiving voltage (V): 394.137677593
Resistance (Ω/km): 16.9230670984
|
| 5 |
Conductor material = Custom measured resistance
Circuit type = DC or single-phase
Wire gauge (AWG) = 12 AWG
Length unit = Metres (m)
Resistance (Ω/km) = 2
Current (A) = 10
One-way distance = 50
Source voltage (V) = 120
|
Voltage drop (V): 2
Voltage drop (%): 1.66666666667
Receiving voltage (V): 118
Resistance (Ω/km): 2
|
| 6 |
Conductor material = Custom measured resistance
Circuit type = Balanced three-phase
Wire gauge (AWG) = 12 AWG
Length unit = Metres (m)
Resistance (Ω/km) = 2
Current (A) = 10
One-way distance = 50
Source voltage (V) = 400
|
Voltage drop (V): 1.73205080757
Voltage drop (%): 0.433012701892
Receiving voltage (V): 398.267949192
Resistance (Ω/km): 2
|