Calculator: Single-phase transformer impedance
Enter the labelled inputs to calculate: Current In (A); Equivalent impedance magnitude (Ω); Coefficient Z% (%).
Enter a finite value within the formula’s domain and supported numeric range.
How the calculation works
In=S/Vn; Zeq=Vsc/In; Z%=100Vsc/Vn
Ideal lumped components are assumed. Parasitics, saturation, mutual inductance, losses and switching ripple are excluded unless explicitly included in the formula.
Values must satisfy the formula’s domain. Nonzero results too small or too large for reliable representation are rejected.
Frequently asked questions
How is the result calculated?
In=S/Vn; Zeq=Vsc/In; Z%=100Vsc/Vn
What assumptions apply?
Ideal lumped components are assumed. Parasitics, saturation, mutual inductance, losses and switching ripple are excluded unless explicitly included in the formula.
How precise are the displayed results?
Numerical results show up to ten significant digits. Rounding does not improve the accuracy of the input measurements or the model. Values must satisfy the formula’s domain. Nonzero results too small or too large for reliable representation are rejected.
How we verified this calculator
The calculator is checked against 3 reference cases computed independently of its code. Last passed: .
| # | Inputs | Expected result |
|---|---|---|
| 1 |
Apparent power S (VA) = 1000
Voltage Vn (V) = 230
Voltage Vsc (V) = 9.2
|
Current In (A): 4.347826087
Equivalent impedance magnitude (Ω): 2.116
Coefficient Z% (%): 4
|
| 2 |
Apparent power S (VA) = 50000
Voltage Vn (V) = 400
Voltage Vsc (V) = 24
|
Current In (A): 125
Equivalent impedance magnitude (Ω): 0.192
Coefficient Z% (%): 6
|
| 3 |
Apparent power S (VA) = 250
Voltage Vn (V) = 12
Voltage Vsc (V) = 0.6
|
Current In (A): 20.83333333
Equivalent impedance magnitude (Ω): 0.0288
Coefficient Z% (%): 5
|