Radiator Temperature Power Scenario

Apply an entered power-law exponent to rated output and a chosen water temperature regime.

Actual mean water-to-room difference (K)
50
Estimated output per radiator (W)
1000
Whole identical radiators
2
Estimated combined output (W)
2000

Calculation and assumptions

ΔT = (T_supply+T_return)/2−T_room; P = P_rated(ΔT/ΔT_rated)^n; N = ⌈P_required/P⌉.

Use rated data and exponent for the actual product. The example n=1.3 is not universal and does not reproduce every manufacturer table. Supply must be at least return, and return above room temperature. This arithmetic-mean power-law scenario excludes flow, installation, controls and room heat-loss calculation; verify product output separately.

Values must satisfy the formula’s domain. Nonzero results too small or too large for reliable representation are rejected.

Frequently asked questions

How is the result calculated?

ΔT = (T_supply+T_return)/2−T_room; P = P_rated(ΔT/ΔT_rated)^n; N = ⌈P_required/P⌉.

What assumptions apply?

Use rated data and exponent for the actual product. The example n=1.3 is not universal and does not reproduce every manufacturer table. Supply must be at least return, and return above room temperature. This arithmetic-mean power-law scenario excludes flow, installation, controls and room heat-loss calculation; verify product output separately.

How precise are the results?

Results show up to ten significant digits. Display precision does not improve the accuracy of the measurements or model. Values must satisfy the formula’s domain. Nonzero results too small or too large for reliable representation are rejected.

How we verified this calculator

The calculator is checked against 3 reference cases computed independently of its code. Last passed: .

# Inputs Expected result
1
Rated output of one radiator (W) = 1000
Rated mean water-to-room difference (K) = 50
Supply temperature (°C) = 75
Return temperature (°C) = 65
Room temperature (°C) = 20
Entered radiator exponent n = 1.3
Entered required heat output (W) = 2000
Actual mean water-to-room difference (K): 50
Estimated output per radiator (W): 1000
Whole identical radiators: 2
Estimated combined output (W): 2000
2
Rated output of one radiator (W) = 1500
Rated mean water-to-room difference (K) = 50
Supply temperature (°C) = 55
Return temperature (°C) = 45
Room temperature (°C) = 20
Entered radiator exponent n = 1.33
Entered required heat output (W) = 1800
Actual mean water-to-room difference (K): 30
Estimated output per radiator (W): 760.3830409
Whole identical radiators: 3
Estimated combined output (W): 2281.149123
3
Rated output of one radiator (W) = 800
Rated mean water-to-room difference (K) = 60
Supply temperature (°C) = 70
Return temperature (°C) = 50
Room temperature (°C) = 21
Entered radiator exponent n = 1.25
Entered required heat output (W) = 3000
Actual mean water-to-room difference (K): 39
Estimated output per radiator (W): 466.9083952
Whole identical radiators: 7
Estimated combined output (W): 3268.358766